Dry-type power transformer

35kV epoxy-resin cast dry-type power transformer

Compact in size and lightweight, it can be installed directly at the load center, reducing civil engineering costs.

Keywords:

35kV epoxy-resin cast dry-type power transformer
35kV epoxy-resin cast dry-type power transformer
+
  • 35kV epoxy-resin cast dry-type power transformer
  • 35kV epoxy-resin cast dry-type power transformer

Technical Performance


Technical Specification

35kV epoxy‑resin cast dry‑type transformer (models SCB/SC series), with core components compliant with GB/T 10228, GB 1094.11, and IEC 60076 standards. It is a three‑phase indoor unit rated for 50 Hz, available in capacities from 30 kVA to 25,000 kVA, with voltage ratings of 35 kV ±2.5% / 0.4 kV (or 10 kV). Insulation class: F (155°C) / H (180°C). Cooling methods: AN (natural air cooling) / AF (forced air cooling). Protection levels: IP20 / IP23.

Performance Features

• Fire Safety: The epoxy resin is flame-retardant and self-extinguishing (UL94 V‑0 rating), oil-free, and free from explosion risks, making it suitable for high-rise buildings, subways, data centers, and other such environments.

• Reliable insulation: Vacuum casting ensures bubble-free construction, with partial discharge levels ≤10 pC; it is moisture- and dust-proof, capable of operating in 100% relative humidity, and requires no drying or preheating upon shutdown.

• High mechanical strength: The windings are fully cast, providing strong resistance to short circuits, withstanding sudden short-circuit electromagnetic forces and exhibiting excellent seismic performance.

• Energy-efficient and low-noise: The core is made of high-quality silicon steel laminations, reducing no-load losses by 5% compared to conventional products, with noise levels as low as 50–60 dB(A).

• Maintenance-free: Oil-free system, no need to monitor oil quality or level, low maintenance costs, and a design life of ≥25 years.

• Strong overload capability: With AF forced air cooling, it can operate continuously at 120% of rated load and withstand short-term overloads up to 150%.

• Flexible installation: Compact and lightweight, it can be placed directly at the load center, reducing civil engineering costs.


Precautions

Please inquire.

Warranty period

Please inquire.

Details and Specifications


Typical SCB13 Series

Basic Electrical Parameters

Insulation and Temperature Rise

Loss and Noise  
(2500 kVA typical value)

Environment and Structure

Rated capacity

30~25000kVA
(Commonly used: 800–5,000 kVA)

Insulation Class

Class F (155°C) /
Class H (180°C)

No-load loss

≈3.2kW

Ambient temperature

-5℃~+40℃ (indoor)

Rated voltage

High voltage 35 kV
(±2 × 2.5% tap)
Low voltage 0.4 kV (or 10 kV)

Temperature Rise Limit

Coil ≤ 100K (Class F),
Iron core ≤ 80K

Load loss (75°C)

≈19kW

Altitude

1000m
(De-rating required at high altitudes)

Connection Group

Dyn11 (mainstream) / Yyn0

Cooling method

AN (Natural Air Cooling) /
AF (Forced Air Cooling, 30% Increased Capacity)

No-load current

≤0.8%

Protection rating

IP20 (protected against finger contact) /
IP23 (drip-proof)

Rated frequency

50Hz

 

 

Noise

≤58dB (A)

Dimensions (2500 kVA)

Approx. 2200×1200×1800 mm

Short-circuit impedance

6%~8%
(400V side)

 

 

 

 

Weight (2500 kVA)

Approximately 3,800 kg

Insulation level

LI170AC70/AC3
(35kV side)

 

 

 

 

 

 

The data in the table are for reference only; the company reserves the right to modify the data and accepts special orders.